PATENTED DUAL-PROBE CHLORINE MONITOR SYSTEM
The dual-probe chlorine monitor/controller systems (DPCMS1) are complete systems designed to alarm when free chlorine is present in the pre-RO feed water and/or the patient loop water. The units include auto-dialing should there be chlorine detected, a facility power failure, or flood (auxiliary input) is detected.
System Features
- Simplistic design with a minimum number of components to minimize installation;
- Easy installation into existing water treatment system;
- High accuracy — +/- 0.02 ppm, repeatability — +/- 0.01 ppm;
- Free chlorine-specific probes (not secondary methods of indication);
- No high maintenance chemical reagents (uses polarographic membranes);
- Four-channel auto-dialer monitors for alarm alerts:
- Water Treatment System Electrical Power (110 vac)
- Both Free Chlorine Monitors
- An Additional Auxiliary Monitor such as Flood Monitor
- Stores up to 8 telephone/pager numbers;
- Makes up to 9 calling efforts for the numbers dialed (when there is no answer or busy);
- Program up to 3 message repeats;
- Each monitor channel has a unique message and specific telephone numbers;
- Contacts for remote alarms;
- Lockable disinfection switch;
- Contacts for actuating divert systems.
Model Key